In all different types of cooling towers drift eliminators are used to reduce the loss of water and emissions. Above the water distribution and the cooling fills, a layer of drift eliminators is installed for this purpose. It catches the water drops which are carried away with the air flow and redirects them into the cooling water circuit.
2H Drift Eliminators are available in two different types. The profile (TAP 160) is mostly used in bigger, the chamber types (TEP 130 and TEC 130) in smaller cooling towers.
Technical Data
TEP 130 | TEC 130 | TAP 160 with Spacer TAS 033
| |
Material | PP | PVC | PP
|
Max. length / width (mm) | 2400 / 700 | 2400 / 800 | 6000 / 330
|
Height (mm) | 125 / 250 | 125 / 250 | 160
|
Drift loss* (%) | ≥ 0.0007 - 0.0005 | ≥ 0.0007 - 0.0005 | ≥ 0.0012 - 0.0006
|
Contin. operation temp. / Max. operation temp. (C°) | 70 / 80 (short time) | 55 / 60 (short time) | 70 / 80 (short time)
|
Max. face velocity (m/s) | 4.5 | 4.5 | 4.0
|
Drag coefficient | 2.2 | 2.2 | 2.6
|
Pitch (mm) | 18 | 18 | 33 / 38
|
Max. distance between supports (mm) | 1000 | 1000 | 1200 |
* Based on the CTI ATC-140 test method (Drift Test Code) and EUROVENT standard OM-14-2009. These limits are guidelines only. The performance of the drift eliminators is indicated by the ratio drift loss/water flow rate. The efficiency of droplet separation depends on constant air velocity and an absolutely tight assembly of drift eliminator elements.