GEA Heat Exchangers / Global

You are here:

2H Fills and Nozzles for Cross-Flow Cooling Towers

Optimal heat transfer properties – low pressure drop

Generally, every cross fluted fill could be cut to be installed in a cross-flow cooling tower. Such a fill, however, would not perfectly fit the requirements; we therefore developed a special range of fill for this type of tower (FX12.12 or KSN with a drift eliminator section KSA and air inlet louvre section KSB).

  • FX12.12 Cross-Flow Cooling Tower Fills
  • KSN 612 Cross-Flow Cooling Tower Fills
  • KSN 619 Cross-Flow Cooling Tower Fills
  • KSN 627 Cross-Flow Cooling Tower Fills
  • Water Distribution Nozzles SPN Series

Installation depths (air travel distance) and inclination vary with each brand of cooling tower. 2H offers fill depths of 12" and 24". Combinations of these allow different installation depths (e.g. 12" + 24" = 36"). In most cross-flow cooling towers the fills are vertically installed at a certain angle (e.g. 10°). The 2H cross-flow cooling tower fills are cut to the required angle of inclination upon customer request.

Blocks with the integral drift eliminators (KSA) must be installed at the air outlet side (inside of the tower). The straight channels are directed upwards in the direction of flow. 2H fills have been shown to meet all drift eliminator requirements at air speeds between 1 and approx. 3.5 m/s. To avoid any risk when operating above this air speed, it is suggested an extra drift eliminator be installed at a distance of 12" behind the KSA fill. The best type for this purpose is the TEP 130 drift eliminator. Blocks with the integral air inlet louvre (KSB) must be installed at the air inlet side of the tower. The straight channels are directed downwards in the direction of flow. Depending on installation depth in the cooling tower, a KSN type fill can be installed between KSA and KSB fill (see sketch). Due to its corrugation geometry the FX12.12 could be installed vertically without inclination. At air velocities higher than 3.2 m/s a small inclination of 2° is required.

Installation example
    • Cross-Flow Tower Fills
    • Technical Data
       
      FSX12.12
      KSN 612
      KSN 619
      KSN 627
      Material
      PVC
      PP
      PP
      PP
      Specific surface height [ft²/ft³]
      74
      73
      46
      38
      Corrugation height [mm]
      12
      12
      19
      27
      Max. installation height [inch]
      94"
      87"
      87"
      87"
      Max. width [inch]
      24"
      24"
      24"
      24"
      Installation depth [inch]
      12 / 24 / 35
      12 / 24
      12 / 24
      12 / 24
      Continuous operating temperature[°F]
      131
      176
      176
      176
      Max. application temp. [°F]
      140
      194
      194
      194
      Void ratio [%]
      > 97
      > 97
      > 97
      > 97
    • Water Distribution Nozzles
    • We offer water distribution nozzles for cooling towers, humidifiers, scrubbers, air coolers and aerators. These nozzles are made of glass fiber reinforced polyamide (nylon). Being correctly assembled, the axial nozzles distribute the water with a spray angle of 120°, providing optimum water distribution above the cooling tower packing.

      • Axial nozzle designed as complete cone spiral nozzle which consists of a casing and an insert.
      • After correct assembly the nozzle distributes the water with a spray angle of 120°.
      • The water flow rate depends on the operational pressure.
      • The arrangement in the plant, i.e. nozzle distance and height, is dependent on the respective plant design.

      Advantages of the SPN Nozzles:

      • Optimum water distribution
        Full cone nozzle with maximum spray angle of 120°
      • Low clogging and scaling tendency
        Due to smooth surface design
      • Constant self-cleaning
        By high turbulence in the nozzle body
      • Easy installation onto the piping system
        Due to BSP thread and hexagon body design
      • High resistance to a large range of chemicals
        Nozzles are made of glass reinforced polyamide (nylon)
    • Technical Data
       
      SPN 015
      SPN 020
      SPN 025
      Material
      glass reinforced polyamide (nylon)
      Thread ISO 228/1 [inch]
      1½
      2
      2½
      Thread height [mm]
      17.5
      19
      28
      Total nozzles height [mm]
      48
      60
      75
      Spanner width [mm]
      50
      65
      80
      Spray angle [°]
      120
      120
      120
      Operation pressure [bar]
      0.2 - 2.0
      0.2 - 2.0
      0.2 - 2.0
      Permanent service temp. [°C]
      60
      60
      60
      Max. application temp. [°C]
      80
      80
      80