CMC

Polacel CMC Series

Counter-Flow Modular Cooling Tower

Print

The Polacel CMC systems combine a high cooling capacity with low energy consump­tion. The modules are supplied ready to use and they are easy to adjust to cooling require­ments and the available space, whether they are used singly or in series. The cooling perfor­mance of these cooling towers is optimal and operation is problem free. With a 95%+ saving in water, the efficient CMC systems are the best choice for man and his environ­ment.

  • Polacel CMC Series Modular Cooling Tower
    Polacel CMC Series
  • Polacel CMC Series
    Polacel CMC Series
  • Polacel CMC Series
    Polacel CMC Series
  • Polacel CMC Series
    Polacel CMC Series
  • Polacel CMC Series
    Polacel CMC Series
  • Polacel CMC Series
    Polacel CMC Series
  • Polacel CMC Series
    Polacel CMC Series
  • Polacel CMC Series
    Polacel CMC Series
  • Polacel CMC Series
    Polacel CMC Series
  • Polacel CMC Series
    Polacel CMC Series
  • Polacel CMC Series
    Polacel CMC Series
  • Polacel CMC Series
    Polacel CMC Series
  • Polacel CMC Series
    Polacel CMC Series

The effect of coun­ter flow

CMC cooling towers work on the prin­ciple of counter flow. This means that the water flows down while the air is pulled upwards by a fan. As the water flows further through the system, the air it encoun­ters is fresher, in other words cooler and less satu­rated with moisture.

Counter flow cooling towers can approach the wet bulb tempe­rature better compared with cross flow cooling towers.

The secu­rity of quality

We design and manu­fac­ture cooling towers with long life­times and minimal mainte­nance needs. This is achieved through the materials used - stainless steel combined with glass fibre and plastic - the sound design and the expe­rience of our engi­neers.

'Cheap and cheerful' solu­tions, such as a fan with a V-belt drive or painted panels, are avoided. The result is a cooling tower that is low mainte­nance, energy effi­cient and able to supply constant excellent problem-free perfor­mance.

    • Type
      CMC1
      CMC2
      CMC4
      CMC6
      CMC9
      CMC12
      CMC16
      Wet surface (m²)
      0.8
      1.5
      2.9
      4.3
      6.3
      8.3
      10.9
      Q min (m³/h)
      6
      11
      20
      30
      44
      58
      76
      Q max (m³/h)
      28
      53
      102
      151
      221
      291
      382
      Lenght (mm)
      940
      1,740
      1,740
      2,540
      2,540
      3,340
      3,340
      Width (mm)
      940
      940
      1,740
      1,740
      2,540
      2,540
      3,340
      Height (mm)
      3,075
      2,775
      3,055
      3,055
      4,050
      4,175
      4,575
      Weight empty (kg)
      270
      310
      670
      900
      1,260
      1,610
      2,090
      Weight operational (kg)
      540
      690
      1,780
      2,690
      4,050
      5,410
      7,230
      Drive type
      direct
      direct
      indirect
      indirect
      geared motor
      geared motor
      geared motor